pet incinerator deisel

 

The charging system shall include, as a minimum, a hopper for top feeding and mechanically operated hydraulic

 

charging pliers or augur. To prevent warpage or excessive thermal expansion, a charger cooling system using either

 

atmosphere or water shall be supplied.

 

Primary combustion chamber shall be either the rotary- or stationary fixed-hearth (or kiln) type incinerator. Burner

 

and combustion air controllers shall be fully automatic comprising of, as a minimum, digital ignition and all

 

necessary interlocks and safety devices to provide safe operation. The chamber and burner shall be made to

 

keep a minimum combustion temperature of at least 700 to 870 C (1300 to 1600 F), but shall not to exceed 980

 

C (1800 F). The ash-removal system shall consist of the automatic continuous removal of the ash into an ashquench

 

pit in which cooled by water and removed by conveyor.

pit where cooled by water and removed by conveyor.