GENERAL SPECIFICATIONS FOR BURNERS

lnsulation: lnsulation to be utilized for stonework, increased concrete, or non-combustible product will protect against damages to the structure from intense warm and shall be of a depth to restrict the outside casing to an optimum temperature of 66 ° C in an ambient temperature of 21 ° C once the burner is running at full ability.

Refractory: Refractory shall be #super obligation # as well as heat-resistant to a minimum of 1100 ° C in the key chamber as well as 1250 ° C in the secondary chamber. Refractory will also be abrasion immune in the prlmary chamber, constructed of plastic or castable kind refractory, designed to stop protruding and also destruction because of warmth stress, efficient in sustaining more than twice the per hour burning rate as well as protecting against leakage of fluids, and also with a minimum thickness of 11O mm for walls and also fireplaces

1. Be accepted as the key burning zone.
Other burning approaches will be assessed on advantages.

3. Ensure main air supply is controlled successfully

Ensure minimum leave temperature level is not much less than 850oC

Air supply: Air supply in the key and second chamber have to be controlled in between 30% -80% as well as 170%- 120% of stoichiometric amount specifically. Suitable circulation measurement devices will be given on the primary and second air ducting. The combustion air will be provided via a different forced draft fan after accounting for the atmosphere provided via burners.The second combustion chamber have to:

1. Be accepted as second combustion area.

Main and added burners: Different electrically spark-ignited main heaters in addition to secondary heaters with automatic control will be made use of to accomplish the specified temperature needs in the main and also added chambers. The fires of the main and also secondary heaters will not hit the burner wall surfaces or flooring.
6. Make certain the gas temperature level as gauged against the inside wall in the secondary chamber & & not in the fire area, is not much less than 1100oC.

7. Make certain the oxygen web content of the given off gases is less than 11%.
2. Be fitted with added burner/s burning gas or low sulphur liquid gas or any type of ideal fuel.

3. Guarantee added air supply is controlled successfully.

4. Make sure fire telephone with all gases is attained.

5. Ensure house time is not much less than 2 (2) secs.